ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 203
3.3
Communication objects
3.3.1
Summary of communication objects
No.
Functionality
Name
Data Point
Type (DPT)
Length
Flags
C
R
W T
U
0
In operation
General
1.002
1 bit
x
x
x
1
Request status values
General
1.017
1 bit
x
x
x
2
Block manual operation
General
1.003
1 bit
x
x
3
Status Manual operation
General
1.003
1 bit
x
x
x
4
Status byte
General
Non DPT
1 byte
x
x
x
5
Fault (overload/short-circuit)
Output A
Output A/B
1.005
1 bit
x
x
x
6
Reset malfunction
Output A
Output A/B
1.015
1 bit
x
x
x
7
Fault (overload/short-circuit)
Output C
Output C/D
1.005
1 bit
x
x
x
8
Reset malfunction
Output C
Output C/D
1.015
1 bit
x
x
x
9
2nd control value, cooling, continuous (PWM)
Output A
Output A/B
5.001
1 byte
x
x
2nd control value, cooling, continuous (3-point)
Output A
Output A/B
5.001
1 byte
x
x
2nd control value, cooling, analog (0...10 V)
Output A
5.001
1 byte
x
x
10
Control value, heating, ON/OFF
Output A
1.001
1 bit
x
x
Control value, heating, continuous (PWM)
Output A
5.001
1 byte
x
x
Control value, heating, continuous (3-point)
Output A/B
5.001
1 byte
x
x
Control value, heating, analog (0...10 V)
Output A
5.001
1 byte
x
x
11
Status Control value
Output A
Output A/B
5.001
1 byte
x
x
x
Status Control value
Output A
Output A/B
1.011
1 bit
x
x
x
12
Fault control value
Output A
Output A/B
1.005
1 bit
x
x
x
13
Activate purge
Output A
Output A/B
1.003
1 bit
x
x
14
Status Valve purge
Output A
Output A/B
1.003
1 bit
x
x
x
15
Priority 1, Forced operation
Output A
Output A/B
1.001
1 bit
x
x
Priority 1, Block
Output A
Output A/B
1.001
1 bit
x
x
16
Priority 2, Forced operation
Output A
Output A/B
1.001
1 bit
x
x
Priority 2, Block
Output A
Output A/B
1.001
1 bit
x
x
17
Priority 3, Forced operation
Output A
Output A/B
1.001
1 bit
x
x
Priority 3, Block
Output A
Output A/B
1.001
1 bit
x
x
18
Status byte
Output A
Output A/B
Non DPT
1 byte
x
x
x
19
Not assigned