ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 151
Function Time on OFF
Options:
None
Switching delay
Minimum time
This defines the
Time
function on Fan OFF.
None
: No
Time
function is executed.
Switching delay
: The fan is switched off after this delay.
Minimum time
: The fan remains OFF for at least this time.
Selection of option
Switching delay
:
Dependent parameter:
Time in s [1…65,535 x 0.1]
Options:
1…20…65,535
The fan is switched off after this delay.
Selection of option
Minimum time
:
Dependent parameter:
Time in s [1…65,535]
Options:
1…20…65,535
The fan remains OFF for at least this time.
Enable communication object
"Forced operation" 1-bit
Options:
No
Yes
Yes
: A 1 bit
Forced operation
communication object is enabled.
Dependent parameters:
Forced operation on object value
Options:
0
1
0
: Forced operation is activated by a telegram with value 0.
1
:
Forced operation is activated by a telegram with value 1.
Reaction on forced operation
Options:
Unchanged
OFF
ON
This parameter defines how the fan should respond to a forced operation.