FCA/S 1.x.x.1 | 2CDC508134D0202 177
Internal connection
Options:
No
Output E
Output F
Output G
Output H
With this parameter, a direct connection of the binary input with an output can be established. With
this connection, no assignment of the group address is necessary.
Output E...H:
The communication object
Switch
of the output is updated together with the
communication object
Switch 1
of the input.
Attention
If an internal connection with an output is selected, and at the same time the reaction to an event
is parameterized with toggle, the communication object
Switch 1
of the input is updated with the
inverted value of the communication object
Status Switch
of the output.
Ensure that the communication object
Status Switch
of the output is enabled. The settings
normally closed contact/normally open contact
and
Invert status
should be parameterized, so
that a toggle function is possible.