ABB i-bus
®
KNX
Commissioning
168 2CDC508134D0202 | FCA/S 1.x.x.1
Restart of staircase time after end
of permanent ON
Options:
No
Yes
No
: The lighting switches off if
Permanent ON
is ended.
Yes
: The lighting remains on and the staircase lighting time restarts.
The function of Permanent ON is controlled via the
Permanent ON
communication object value. If
the communication object receives a telegram with the value 1, the output is switched on regardless
of the value of the communication object
Switch
and remains switched on until the communication
object
Permanent ON
has the value 0.
Object value "Disable function Time"
after a download
Options:
Unchanged
0 = enable function Time
1 = Disable function Time
This parameter defines how the function
Time
should react after a download. With a telegram to the
communication object
Disable function Time
, the function
Time
can be disabled.
Unchanged:
The function
Time
can continue unchanged.
Note
The state of the
Time
function is stored with bus voltage failure and continues unchanged after
bus voltage recovery.
0 = Enable function Time:
The
Time
function is enabled by a telegram with the value 0.
Note
If the staircase lighting is disabled when the function
Time
is operational, the light will stay at ON
until it is switched to OFF manually.
1 = Disable function Time
: The
Time
function is disabled by a telegram with the value 1.
Note
Enabling is only possible via the communication object
Disable function Time
.