ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 153
Enable communication object
"Status Fan On/Off" 1-bit
Options:
No
Yes
This parameter enables the communication object
Status Fan ON/OFF
.
Some fans initially require an ON telegram before they are set to a fan speed from the OFF state. This ON
telegram has effect on a main switch which has to be switched on. This requirement can be implemented
with any switch output controlled via the
Status Fan
communication object. The corresponding
communication object
Switch
of the switch actuator should be connected with the
Status Fan
communication object.
Selection of option
Yes
:
Dependent parameter:
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only
: The status is updated but not sent.
On change
: The status is sent when a change occurs.
After request
: The status is sent when a request occurs.
After a change or request
: The status is sent on a change or a request.
The following parameter is only visible if the option
Yes
has been selected in the
Enable automatic
operation
parameter in the
Fan
parameter window.
Enable communication object
"Status Automatic" 1-bit
Options:
No
Yes
This parameter enables the communication object
Status Automatic
.
Telegram
value:
1 = Automatic operation active
0 = Automatic operation inactive
Selection of option
Yes
:
Dependent parameter:
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only
: The status is updated but not sent.
On change
: The status is sent when a change occurs.
After request
: The status is sent when a request occurs.
After a change or request
: The status is sent on a change or a request.