Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 131
Enable communication object
"Status Fan speed" 1-byte
Options:
No
Yes
This status byte defines the figure value of the fan speed.
This display can be differentiated from
Required fan speed
by selecting
Current fan speed
. Initially, the
switchover times, dwell times and start-up phase must be completed before the required fan speed is
reached.
Yes
: The communication object
Status Fan speed
is enabled.
Dependent parameters:
Meaning 1 byte
Options:
Current fan speed
Required fan speed
This parameter defines which status
–
Current fan speed
or
Required fan speed
– is displayed.
What is current fan speed?
The
Current fan speed
is the speed at which the fan is actually operating.
What is required fan speed?
The
Required fan speed
is the fan speed which has to be reached, e.g. when the transition
and dwell times have elapsed.
Note
The limitations are included in this observation, i.e. if a limitation allows only fan speed 2,
the fan is operating at fan speed 2, and, for example, a telegram to switch up is received,
the required fan speed remains at 2, as fan speed 3 cannot be reached due to the
limitation.
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only
: The status is updated but not sent.
On change
: The status is sent when a change occurs.
After request
: The status is sent when a request occurs.
After a change or request
: The status is sent on a change or a request.