ABB i-bus
®
KNX
Commissioning
150 2CDC508134D0202 | FCA/S 1.x.x.1
Fan speed on bus voltage recovery
Options:
Unchanged
OFF
ON
The reaction of the fan on bus voltage recovery is defined here.
Unchanged
: The fan speed remains the same.
OFF
: The fan is switched off.
ON
: The fan is switched on.
Attention
The device is supplied ex-works with a default setting (factory default). This ensures that the fan setting
is switched off when the bus voltage is applied to the relay for the first time. Thus, damage to the device
due to unintentional switch on during transport, e.g. due to vibration, is avoided.
It is advisable to apply a bus voltage before connecting the fan in order to assign it a defined switch
state. This eliminates the possibility of an incorrect contact setting destroying the fan.
Enable automatic operation
Options:
No
Yes
Yes: Automatic operation
also appears.
Function Time on ON
Options:
None
Switching delay
Minimum time
This defines the
Time
function on Fan ON.
None
: No
Time
function is executed.
Switching delay
: The fan is switched on after this delay.
Minimum time
: The fan remains ON for at least this time.
Selection of option
Switching delay
:
Dependent parameter:
Time in s [1…65,535 x 0.1]
Options:
1…20…65,535
The fan is switched on after this delay.
Selection of option
Minimum time
:
Dependent parameter:
Time in s [1…65,535]
Options:
1…20…65,535
The fan remains ON for at least this time.