ABB i-bus
®
KNX
Device technology
FCA/S 1.x.x.1 | 2CDC508134D0202 55
2.4.9
Output, lamp load 20 AX
Lamps
Incandescent lamp load
3,680 W
Fluorescent lamps T5/T8
Uncompensated
Parallel compensated
DUO circuit
3,680 W
2,500 W
3,680 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
2,000 W
2,500 W
Halogen lamps 230 V
3,680 W
Dulux lamp
Uncompensated
Parallel compensated
3,680 W
3,000 W
Mercury-vapor lamp
Uncompensated
Parallel compensated
3,680 W
3,680 W
Switching capacity (switching contact)
Maximum peak inrush current I
p
(150
s)
600 A
Maximum peak inrush current I
p
(250
s)
480 A
Maximum peak inrush current I
p
(600
s)
300 A
Number of electronic ballasts (T5/T8, single
element)
1)
18 W (ABB EVG 1 x 18 SF)
26
2)
24 W (ABB EVG-T5 1 x 24 CY)
26
2)
36 W (ABB EVG 1 x 36 CF)
22
58 W (ABB EVG 1 x 58 CF)
12
2)
80 W (Helvar EL 1 x 80 SC)
10
2)
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the ballasts.
2)
Limited by protection with B16 automatic circuit-breaker.