ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 181
3.2.4.3
Parameter window a: Value/forced operation
This operating mode allows the sending of values of any data types.
This parameter window is visible if the option
Value/forced operation
has been selected in the parameter
Input a
Maximum dead time
This parameter is fixed to a preset 250 ms.
The maximum dead time prevents unwanted multiple operations of the input, e.g. due to bouncing of the
contact.
What is the maximum dead time?
An edge change at the input is assessed with a maximum dead time (delay) value of 250 ms. This
time may vary from 0 ms to 250 ms.
Note
No further bouncing is possible.