ABB i-bus
®
KNX
Commissioning
206 2CDC508134D0202 | FCA/S 1.x.x.1
No.
Functionality
Name
Data Point
Type (DPT)
Length
Flags
C
R
W T
U
80
Switch
Output H
1.001
1 bit
x
x
81
Permanent on
Output H
1.003
1 bit
x
x
82
Disable function Time
Output H
1.003
1 bit
x
x
83
Status Switch
Output H
1.001
1 bit
x
x
x
84…89
Not assigned
90
Block
Input a: Switch sensor
1.003
1 bit
x
x
Input a: Value/forced operation
1.003
1 bit
x
x
Output value
Input a: Temperature sensor
9.001
2 byte
x
x
x
91
Switch 1
Input a: Switch sensor
1.001
1 bit
x
x
x
Value 1
Input a: Value/forced operation
Variable
x
x
Request output value
Input a: Temperature sensor
1.009
1 bit
x
x
92
Switch 2
Input a: Switch sensor
1.001
1 bit
x
x
x
Value 2
Input a: Value/forced operation
Variable
x
x
Measured value out of range
Input a: Temperature sensor
1.001
1 bit
x
x
x
93
Switch 3
Input a: Switch sensor
1.001
1 bit
x
x
x
Threshold 1
Input a: Temperature sensor
Variable
x
x
x
94
Start event 0/1
Input a: Switch sensor
1.001
1 bit
x
x
Change Threshold 1 lower limit
Input a: Temperature sensor
Variable
x
x
x
95
Change Threshold 1 upper limit
Input a: Temperature sensor
Variable
x
x
x
96
Threshold 2
Input a: Temperature sensor
Variable
x
x
x
97
Change Threshold 2 lower limit
Input a: Temperature sensor
Variable
x
x
x
98
Change Threshold 2 upper limit
Input a: Temperature sensor
Variable
x
x
x
99
Not assigned
100…109
Input b
The same CO as Input a
110…119
Input c
The same CO as Input a
120
Toggle heating
General
1.100
1 bit
x
x
121
Valve control values parallel mode
General
1.100
1 bit
x
x