ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 187
Value 1 (event 0 or
on short operation)
Options:
Do not send
1-bit value [0/1]
2-bit value (forced operation)
1-byte value [-128...127]
1-byte value [0...255]
1-byte value (8-bit scene)
2-byte value [-32,768...32,767]
2-byte value [0...65,535]
2-byte value (floating point)
4-byte value (floating point)
3-byte value (time of day/weekday)
4-byte value [-2147483648...2147483647]
4-byte value [0...4294967295]
This parameter serves for defining the data type which is sent when the contact is actuated.
Note
With the setting 2-byte value (floating point), rounding off errors can occur, meaning that the value sent
to the bus may not correspond precisely to the set value. If a high degree of precision is required, select
the option 4-byte value (floating point).
Depending on the selection made in the parameter
Value 1
, different parameters will appear. All
parameters are described in the following:
Sent value [X]
Options:
ON/OFF/TOGGLE
0/1
-
128…0…127
0
…255
-
32,768…0…32,767
0
…65,535
-
100…0…100
-
2147483648…0…2147483647
0
…4294967295
This parameter defines the value which is sent on operation. The value range is dependent on the
set data type of the value X.
Sent value (forced operation)
Options:
ON, activate forced operation
OFF, activate forced operation
Disable forced operation
This parameter defines the value which is sent on operation.