Operation mode output C and D
Options:
Individual
Valve drive, motor-driven (3-point)
This parameter determines whether the operation modes of outputs C and D can be parameterized
individually or whether the outputs are operated in operation mode
Valve drive, motor-driven (3-point)
.
The outputs are linked to one another in pairs in this operation mode. Outputs C and D control the
contacts Open/Close of the valve drive for opening/closing the valve.
Individual:
With this setting, the operation modes of outputs C and D are set individually from one
another.
Dependent parameters:
Output C
Output D
Options:
Disabled
Valve drive, thermoelectric (PWM)
This parameter defines the individual operation mode of the output.
Disabled:
No operation mode selected.
Valve drive, thermoelectric (PWM):
The parameter (window) and communication objects for the
operation mode
Valve drive, thermoelectric (PWM)
are enabled.
Valve drive, motor-driven (3-point):
The parameter (window) and communication objects for the
operation mode
Valve drive, motor-driven (3-point)
are enabled.
Output C
Open
Output D
Close
Assignment of the valves
Note
Outputs A and C are automatically assigned via the selection in the parameter
Fan Coil operating mode
.