ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 191
3.2.4.4
Parameter window a: PT100, PT1000 and KTY
3.2.4.4.1
Parameter window a: PT100/PT1000
This operating mode allows the sending of temperature values.
This parameter window is visible if one of the options
PT100
or
PT1000
has been selected in the
parameter
Input a
The
Sensor output
is set with these parameters. The data can be found in the sensor manufacturer's
technical documentation.
Send output value as
This parameter is fixed to
2-byte [EIB floating point]
.
What is the output value?
The Analogue Input records a sensor measured value, converts it according to the set parameters
and sends it on the bus. This sent value is designated as the output value.