ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 163
3.2.3.20
Parameter window H: Output
All settings for output H are made in this parameter window.
This parameter window is visible if
Output H
Reaction of output
Options:
N/O
N/C
This parameter sets whether the output operates as a
normally closed contact
or
normally open contact
.
Normally opened contact
: An ON telegram (1) closes the contact, and an OFF telegram (0) opens the
contact.
Normally closed contact
: An ON telegram (1) opens the contact, and an OFF telegram (0) closes the
contact.
Contact position
on bus voltage failure
Options:
Unchanged
Open
Closed
The output can adopt a defined state on bus voltage failure (BVF) using this parameter.
Open:
The contact is opened with bus voltage failure.
Closed:
The contact is closed with bus voltage failure.
Unchanged:
No change of the contact setting.
Note
Take note of the reaction on bus voltage failure, recovery and download.