ABB i-bus
®
KNX
Commissioning
180 2CDC508134D0202 | FCA/S 1.x.x.1
3.2.4.2.2
Parameter Distinction between long and short operation
– Yes
If the option
Yes
has been selected with the parameter
Distinction between long and short operation
, the
following parameters appear in
Short operation -> Event 0
Long operation -> Event 1
<−−− NOTE
Input on operation
Options:
open
Closed
Open:
The input is opened with actuation.
Closed:
The input is closed with actuation.
If a normally open contact is connected to the input, the option
Closed
should be selected; on a
normally closed contact the option
Open
should be selected.
Long operation after …
Options:
0.6/0.8 s
1/1.2/1.5 s
2/3/4/5/6/7/8/9/10 s
Here the time period T
L
, after which an operation is considered a “long” operation, is defined.
Note
The remaining parameter descriptions can be found in