ABB i-bus
®
KNX
Commissioning
92 2CDC508134D0202 | FCA/S 1.x.x.1
Note
If the options with 2 valves are selected, parallel mode can be enabled via the communication object
Valve control values parallel mode
.
communication object "Valve control
values parallel mode" 1-bit
Options:
No
Yes
Yes:
The 1-bit communication object
Valve control values parallel operation
is enabled.
Note
communication object "Valve control values parallel mode" only operates on Fan Coil valves.
Note
If an operation mode with 2 control values and 1 valve is selected for the Fan Coil, an additional
communication object (no. 9) is enabled that is set for cooling and is as follows, depending on the
operation mode of the outputs:
2nd control value, cooling,
continuous (PWM)
2nd control value, cooling,
continuous (3-point)
2nd control value, cooling,
analog (0...10 V)