FCA/S 1.x.x.1 | 2CDC508134D0202 63
2.6.2
Operating controls
Buttons for manual operation are located on the front of the devices.
The reaction of the operating elements is described in the following table according to the operating states
KNX operation
and
Manual operation
:
Button
KNX operation
Manual operation
Manual operation
Long button push
≥ 1.5 sec.:
Switch to
Manual operation
,
provided that
Manual operation
is not blocked by a
parameter setting.
Short button push
≤ 1.5 sec.:
LED
flashes and switches
off again. The device is in
KNX operation
.
Long button push
≥ 1.5 sec.:
Changeover to
KNX
operation
. The inputs are scanned again. In this way, the
input states are updated.
Resetting the
Manual operation
to
KNX operation
can also
be completed within a parameterized time depending on
the parameterization.
…
Output A…D
Valve drive, motor-driven (3-point) and
valve drive, thermoelectric (PWM)
A fault, e.g. due to an overload/short circuit, is indicated on
the device by flashing (frequency 4.8 Hz) of the
corresponding LED (A+B or C+D).
Short button push
≤ 1.5 sec.:
The reaction of the buttons depends on the mode of
operation:
Valve drive, motor-driven (3-point):
Output: A and C:
Open/STOP
First operation point:
Press:
Valve from 0...100%, then STOP => OPEN
Release:
No reaction
Output: B and D: Close/STOP
Next operation point:
Press:
Valve from 100...0%, then STOP => CLOSED
Release:
No reaction
Long button push
≥ 1.5 sec.:
No function
A characteristic curve adjustment is undertaken, if it is
parameterized.
Valve drive, thermoelectric (PWM):
Output: A, B, C or D:
Open/close
First operation point:
Press:
Valve from 0...100%, then STOP => OPEN
Release:
No reaction
Next operation point:
Press:
Valve from 100...0%, then STOP => CLOSED
Release:
No reaction
Long button push
≥ 1.5 sec.:
No function
A characteristic curve adjustment is undertaken, if it is
parameterized.
or
Long button push (> 2s) on one of the buttons B or D
triggers a valve reference movement
Output A
(Output C)
Valve drive, analog (0...10 V):
A fault, e.g. due to an overload/short circuit, is indicated on
the device by flashing (frequency 4.8 Hz) of the
corresponding LED.
Valve drive, analog (0...10 V):
Short button push
≤ 1.5 sec.:
Press:
Valve from 0...100%, then STOP => OPEN
Release:
No function
Long button push
≥ 1.5 sec.:
No function
A characteristic curve adjustment is undertaken, if it is
parameterized.
Output A
(Output C)
Valve drive, analog (0...10 V):
Short button push
≤ 1.5 sec.:
Press:
Valve from 100...0%, then STOP => CLOSED
Release:
No function
Long button push
≥ 1.5 sec.:
No function
A characteristic curve adjustment is undertaken, if it is
parameterized.