212 2CDC508134D0202 | FCA/S 1.x.x.1
No.
Functionality
communication object name
Data type
Flags
11
Status Control value
Output A
Output A/B
1 byte
DPT 5.001
C, R, T
This communication object is enabled with the option
Yes
via the parameter
Enable communication object "Status control
value"
p. 113, and with selection of the option
Byte
in the parameter
Data type
.
The control status of the output is sent via this communication object. Hereby, the limit position that the valve should assume
is transferred.
The object is not sent in the event of a short circuit, overload, failure of the supply voltage and reference adjustment (only in
operation mode
Valve drive, motor-driven (3-point)
).
The LED of the corresponding output indicates the same value as the status.
Note
Signaling via LED occurs only for the devices FCA/S 1.1.2.2 and FCA/S 1.2.2.2.
The status is sent if:
a request is received via the communication object
Request status values
and the parameter is set to
After request
or
After a change or request
.
the value of the communication object has changed and the parameter is set to
After request
or
After a change or
request
.
a read request is carried out on this communication object.
Telegram value:
0…255 = Control is displayed directly as a figure value
At 0 = LED (yellow) off
At > 0 = LED (yellow) on
11
Status Control value
Output A
Output A/B
1 bit
DPT 1.011
C, R, T
This communication object is enabled with the option
Yes
via the parameter
Enable communication object "Status control
value"
p. 113, and with selection of the option
Bit
in the parameter Data type.
The control status of the output is sent via this communication object.
The LEDs of the corresponding outputs indicates the same value as the status.
The status is sent if:
a request is received via the communication object
Request status values
and the parameter is set to
After request
or
After a change or request
.
the value of the communication object has changed and the parameter is set to
After request
or
After a change or
request
.
a read request is carried out on this communication object.
Telegram value:
0 = Control value equal to zero/LED (yellow) off
1 = Control value not equal to zero/LED (yellow) on