Quickstart with standard actuation
RF
Controller enable
v=0
Hold speed 0
V1
Positioning speed
V3
Travel speed V_3
RV1 / RV2
Direction default
RB
Controller ready
MB_Brake
Mechanical brake
Quick start with DCP actuation
B0
Converter enable
B1
Travel command
B2
Off switch
B3
Travel speed V_3
B4
Direction default
S1
Travel active
S6
Mechanical brake
G2
Speed 0
G7
Travel speed
12.15.2
Monitoring functions for Quickstart
•
If the drive is maintained at speed 0 for longer than 20 s, the frequency inverter enters fault mode
and displays
ERR780/Quickst. t-limit
•
If the input signal "Maintain speed 0" is set during travel, the frequency inverter enters fault mode
and displays
ERR781/Quick. during travel
•
If the motor moves by more than
±
7 mm with the input set to speed 0, the ZETADYN 4 goes to fault
mode, displaying
ERR529 / Quickstart Alarm
•
The monitoring time for the rotary encoder (T_GUE) is started after the function "Speed 0" has
been switched off
Translation of the original operating instructions
ZETADYN 4C
Travel options
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
119/204
1
2
Travel
options
Содержание ZETADYN 4C
Страница 192: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 192 204 ...
Страница 194: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 194 204 ...
Страница 196: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 196 204 ...
Страница 198: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 198 204 ...
Страница 200: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 200 204 ...