14.5.2
Block function
Blocks the controller if certain errors occur several times is succession. The errors must occur in
directly consecutive travel tests. The fault counter is set to 0 when performing a trouble-free run.
The following block functions can be set in the
Monitoring / MOD_ST
menu:
•
Fix 2 Sec.: No blocking function, the output con
fi
gured on "ST" drops for 2 seconds during a
malfunction and then increases again (speed preset V_x must be switched off)
•
Lock n.3: Lock function after 3 malfunctions. Output "ST" remains dropped after the 3rd error
•
Lock n.2: Lock function after 2 malfunctions. Output "ST" remains dropped after the 2rd error
•
Lock n.1: Lock function after 1 malfunction1. Output "ST" remains dropped after the 1st error
Errors which lead to disabling of the ZETADYN 4 are marked by a
dot
in the
S
column.
14.5.3
Notes 0xx
Information about:
•
Error memory content
•
Changes in the operating conditions
•
Application of special frequency inverter functions
Note-No.
Note text
Description
M S
N0
Memory empty
EEPROM is empty
N010
Update software
Software update was carried out
Additional information:
Version of the new software
N020
MOT_TYP changed
Motor type in "Motor name plate" was changed
N077
ST_LST: locked
Five faults occurred in direct succession
Fault memory is blocked
Additional information:
indicates the most recent fault
The fault counter is set to 0 when performing a trouble-free run.
●
N080
Mode: EVA ->Norm
Switchover from evacuation to normal mode was implemented
N081
Mode: Norm ->EVA
Switchover from normal to evacuation to mode was implemented
N082
Mode:ParaChange
The parameter set was changed
●
N085
Mode: Safety Br
Safety brake function was implemented
●
N086
Mode:Enc.Adj.MB
Encoder-alignment with closed brakes was carried out
N087
Mode:Encoder-Adj.
Manual encoder offset was carried out
N088
Mode:Encoder-Check The encoder offset alignment was checked
14.5.4
Error 1xx
•
Hardware con
fi
guration error
•
Software error
Error no.
Error text
Error cause
M S
100
Serial no. missing
Frequency inverter/CU does not have a serial number, e.g. after a component
replacement
●
101
System-Error
A defective internal component was identi
fi
ed during a self-test of the fre-
quency inverter
●
110
120
CU: No ID
CU ID no. was not detected:
CU is not present or its ID EEPROM does not reply
●
111
CUSH: No ID
Shunt ID no. was not detected:
Shunt module is not present or its ID EEPROM does not reply
●
113
123
CUEE: No ID
ID no. of the extension card for the rotary encoder was not detected: extension
module is not present or its ID EEPROM does not reply
●
115
125
SP: No ID
Switching power supply ID no. was not detected: Switching power supply is not
present or its ID EEPROM does not reply
●
116
126
PP: No ID
Power print ID no. was not detected:
Power print is not present or its ID EEPROM does not reply
●
Translation of the original operating instructions
ZETADYN 4C
Error diagnosis
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
132/204
Содержание ZETADYN 4C
Страница 192: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 192 204 ...
Страница 194: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 194 204 ...
Страница 196: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 196 204 ...
Страница 198: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 198 204 ...
Страница 200: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 200 204 ...