5.15.2
CANopenLift
•
A shielded bus-cable is not needed, but the data wires should be twisted.
•
The installation takes place in line structure. The seperate devices are connected to the bus with
short branch lines.
•
The bus should be terminated with a terminating resistor of 120 - 150 Ohms, at both ends of the
bus.
•
The maximum length of the bus is 200 m and 6 m at the branch lines.
CAUTION!
Caution!
Incorrectly wired connections can destroy the electrical / electronic components.
Electrostatic discharges can be hazardous to the electronic components and lead to errors in the
software.
The bus cable is connected by the interface X-CAN at the ZETADYN 4
X-CAN
CL
CH
0VC
CAN High (H)
CAN Low (L)
GND (optional)
(1)
(2)
(3)
(4)
Optionaler
Schirmanschluss
Connection CAN
To activate the terminating resistance, the jumper at terminal J1 must be plugged to the top two pins
(see
fi
g.).
For more detailed information on CANopen lift, see chapter "Serial communication/CANopen lift"
Translation of the original operating instructions
ZETADYN 4C
Electrical installation
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
34/204
Содержание ZETADYN 4C
Страница 192: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 192 204 ...
Страница 194: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 194 204 ...
Страница 196: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 196 204 ...
Страница 198: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 198 204 ...
Страница 200: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 200 204 ...