X-STO
+24V_
STO
GND
STO_A
STO_B
GND_
STO
(6)
(5)
(4)
(3)
(2)
(1)
STO connection bridged
Select the motor contactors depending on the type of motor and the corresponding motor data.
According to DIN EN 81-1, the motor contactor contacts must be self-commutated.
The maximum line length to the motor contactors when using non-shielded lines is
200mm
. If there is
a greater distance between the contactors and ZETADYN 4, you must use shielded lines!
Danger!
Whenoperatingthemotorwithanencoder,the feed line to the motor must be connected on the motor and
inverter side phase-correct: U
R
U / V
R
V / W
R
W.
Never swap the connection; not even if the rotary direction of the motor is false!! If the motor phases
are swapped, motor control is generally not possible. This can lead to jerky movements or uncon-
trolled acceleration of the motor.
X3
V
W
M
3~
V
W
U
P1
P2
U
K1
3 4
1 2
K2
3 4
1 2
Asynchronous motor connection
X3
V
W
M
3~
V
W
U
P1
P2
U
R2 R1
R4 R3
K1
3 4
1 2
K2
3 4
1 2
Synchronous motor connection
Translation of the original operating instructions
ZETADYN 4C
Electrical installation
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
41/204
5
Electrical
instal-
lation
Содержание ZETADYN 4C
Страница 192: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 192 204 ...
Страница 194: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 194 204 ...
Страница 196: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 196 204 ...
Страница 198: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 198 204 ...
Страница 200: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 200 204 ...