ZETADYN 4C
X1
L1
L2
L3
L3
L2
L1
PE
1
Line connection ZETADYN 4C
1
Mains 3~ 400V/PE/50Hz
5.7
Line reactor-radio interference
fi
lter
The line reactor and radio interference
fi
lter integrated into the device ensures compliance with the
product series standards listed below:
•
EN 12015 Electromagnetic compatibility
–
product series standard for lifts, escalators, moving
pavements
–
spurious emission
•
EN 12016 Electromagnetic compatibility
–
product series standard for lifts, escalators, moving
pavements
–
interference immunity
5.8
Residual current operated device (RCCB)
Frequency inverters of the ZETADYN type require no RCD circuit breaker for operation.
The1997circuit0100at4100the output of the ZETADYN C is monitored by an electronic short-circuit
protection. On detecting a short-circuit current at the output of the ZETADYN (and thus negligible
impedance between the phase and a body or the protective earth of the circuit or a protective earth of
the operating medium in the case of an error) the output current is switched off within a time of <20
μ
s.
On condition that the potential equalisation for the ZETADYN and the motor was performed according
to the valid standards (VDE -Part 540:2012-06 and DIN EN 50178:1997), this06behaviour is suf
fi
cient
for the automatic switch off in case of an error demanded by VDE 0100-
If an RCD circuit breaker is required for special reasons (e.g.
fi
re protection), an all current-sensitive
RCD circuit breaker type B must be used. For maximum operational reliability Ziehl-Abegg recom-
mends the use of an RCD circuit breaker with reference fault current 300 mA for
fi
re protection
according to regulation VdS 3501.
Information
Please note that even when using a correct type B RCCB, false triggering due to high protective earth
currents (stray current) can still occur and that operation with these protective devices is not possible.
Translation of the original operating instructions
ZETADYN 4C
Electrical installation
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
24/204
Содержание ZETADYN 4C
Страница 192: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 192 204 ...
Страница 194: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 194 204 ...
Страница 196: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 196 204 ...
Страница 198: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 198 204 ...
Страница 200: ...Translation of the original operating instructions ZETADYN 4C Enclosure R TBA12_01 GB 1415 Part No 00163371 GB 200 204 ...