YX3000 Senseless Vector Type Inverter Manual
- 81 -
P0.15
Time of s curve
ascent stage
Range
:
10.0
%~
80.0
%(
Acc/Dec
),
P0.14
+
P0.15<90
%
60.0
%
P0.14, P0.15 is effective only in s curve Acc/Dec mode(P0.13=1).
S curve start stage time shown as Fig.6-5(3). The curve slope is increasing from 0.
S curve ascent stage time shown as Fig.6-5(2). The curve slope keeps constant.
S curve end stage time shown as Fig.6-5(1). The curve slope is decreasing to 0.
Note:
S curve Acc/Dec mode is suitable for the starting and stopping process of conveying
load such as elevator and belt conveyor, etc.
P0.16
Acc/Dec time unit
Range: 0, 1
0
0: Second
1: Minute
Note:
(1) This function is effective for all Acc/Dec process except for JOG running mode.
(2) Please try to select second as time unit.
P0.17
Acc time 1
Range: 0.1
~
6000.0
20.0
P0.18
Dec time 1
Range: 0.1
~
6000.0
20.0
Acc time is the time of inverter output frequency increasing from 0 to upper limit freq. shown
as in Fig.6-6 t1.
Dec time is the time of inverter output frequency decreasing from upper limit freq. to 0 shown
as Fig.6-6 t2.
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...