YX3000 Senseless Vector Type Inverter Manual
- 144 -
Cut off the power when inverter is maintained thermally, check after the main circuit power
indicator light is off. The checking content is shown in Table 8-1.
table 8-1 Periodic inspections
Checking item
Checking content
Troubleshooting
Screws
of
control
terminals and main circuit
terminals
The screws are loose or not
If loose, tighten them with
screw driver
heat sink
Whether there is dust
Clean thoroughly the dust
P
Printed circuit board
Whether there is dust
Clean thoroughly the dust
Cooling fans
Whether there is abnormal
vibration or abnormal noise
Replace cooling fans
Power element
Whether there is dust
Clean thoroughly the dust
Electrolytic capacitor
Whether there is discoloring,
peculiar smell
Replace
electrolytic
capacitor
8.2.2 Thermally maintaining
In order to let inverter work well for a long term, user must maintain the inverter thermally.
The replace time of element of inverter is shown in Table 8-2.
Table 8-2 frequency inverter parts replacement
Items
Time criterion
Cooling fans
2-3 years
Electrolytic capacitors
4-5 years
Printed circuit board
5-8 years
Fuse
10 years
The working condition of the inverter as following:
(1) Environment temperature: average 30C.
(2) Load coefficient: under 80%.
(3) Running time: under 12 hour everyday.
8.3 Warranty of Inverter
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...