YX3000 Senseless Vector Type Inverter Manual
- 113 -
P4.23
Set counts given
Range: P4.20
~
9999
0
P4.24
Specified counts given
Range: 0
~
P4.19
0
P4.21,P4.22 are the complement to function 12,13 listed in Table 6-6.
Set counts given: It refers to when how many pulse signals input from Xi (count trigger signal
input function terminal), OC (2-way open collector output terminal) or relay outputs an index
signal.
When Xi inputs the 8th pulse signal, OC outputs an index signal, that is P4.21=8, shown as
Fig.6-27.
Specified counts given: It refers to when how many pulse signals input from Xi, OC or relay
outputs an index signal, until set counts arrival.
When Xi inputs the 5th pulse signal, relay outputs an index signal, until set counts 8 arrival,
that is P4.22=5, shown as Fig.6-27. When specified counts bigger than set counts, specified
counts invalid.
。
Fig.6—28 set counts given and specified counts given
P4.25
Overload pre-alarm detection
level
Range: 20
-
200(
%
)
130(%)
P4.26
Overload pre-alarm delay time
Range: 0.0
-
20.0S
5.0S
If output current exceeds continuously current detection level set by P4.23 (the actual
detection level current = P4.23 X inverter rated current), after the delay time set by P4.24, the
open collector outputs valid signal shown as Fig. 6-28 (refer to P4.11).
1
2
3
4
5
6
7
8
9
Xi input
OC1 output
Relay output
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...