YX3000 Senseless Vector Type Inverter Manual
- 137 -
PA.09
Motor stator resistance
Range
:
0.001
~
50.000Ω
Depends on
model type
PA.10
Motor rotor resistance
Range
:
0.001
~
50.000Ω
Depends on
model type
PA.01~PA.10 are defined as motor parameter. The inverter has its own factory default set
parameter which depends on model type. User is able to reset above parameter according to
parameter of motor used. These parameter should be entered correctly, otherwise, the vector
control function can’t achieve desired control effect
PA.11
Over current protection
coefficient of torque current
Range
:
0
~
15
15
In vector control mode, this function is used for controlling torque current as to
prevent over current .The range of 0-15 correspond to 50%-200%.
PA.12
Proportion adjustment coefficient
of speed deviation
Range
:
50
~
120
85
PA.13
Integral adjustment coefficient of
speed deviation
Range
:
100
~
500
360
In vector control mode, PA.12~PA.13 are used for controlling motor rotating speed. It can achieve
better motor speed control effect by proper adjustment of these two function parameter
PA.14
Vector torque boost
Range
:
100
~
150
100
In vector control mode, this function is used to boost output torque of motor.
It can properly increase this parameter in application with heavy load as to
boost output torque of motor.
6.12 Factory Function parameter
:(
PF Group
)
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...