YX3000 Senseless Vector Type Inverter Manual
- 83 -
P0.24
V/F Volt. V3
Range: P0.26
~
100.0
%
0.0
%
P0.25
V/F Freq. F2
Range: P0.27
~
P0.23
0.00Hz
P0.26
V/F Volt. V2
Range: P0.28
~
P0.24
0.0
%
P0.27
V/F Freq. F1
Range: 0.00
~
P0.25
0.00Hz
P0.28
V/F Volt.V1
Range: 0
~
P0.26
0.0
%
These function parameter defines flexible V/F setting mode of inverter. User can select 4
fixed curves and 1 customized curve through P0.22 parameter so as to meet different load
requirements.
P0.22=0, Constant torque V//F curve shown as Fig.6-7 curve 0
P0.22=1, 1.2 times the power reduced torque V/F curve shown as Fig.6-7 curve 1
P0.22=2, 1.7 times the power reduced torque V/F curve shown as Fig.6-7 curve 2
P0.22=3, 2.0 times the power reduced torque V/F curve shown as Fig.6-7 curve 3
When inverter drives reduced torque load such as fans, and pumps, user can select 1/2/3
V/F curve running mode according to load characteristic for energy saving.
Fig 6—7 V/Curve
Output Volt. V
Vmax
:
max output voltage F
b
basic running Freq.
F
b
Vmax
0
0 1
2
3
Output Freq. Hz
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...