YX3000 Senseless Vector Type Inverter Manual
- 88 -
Fig.6-10
Notes:
Start frequency is not restricted by lower limit freq
P2.03
DC brake current as start
Range: 0
~
15(
%
)
0(
%
)
P2.04
DC brake time as start
Range: 0.0
~
60.0S
0.0S
DC brake current is a percentage relative to the inverter rated current. There is no DC brake
as DC brake time is 0.0s.
Fig.6-11 start mode 1
Fig.6-12 DC stop and DC brake
P2.05
Stop mode
Range: 0, 1, 2
0
0: After receiving stop command, the inverter decreases the output frequency to 0 in set Dec
time.
1: After receiving stop command, the inverter stops output immediately, and the load goes to
stop by mechanical inertia. This is called as coast stop.
2
:
After receiving stop command, the inverter decreases the output frequency
in Dec time , when it reaches the start frequency of DC brake, the inverter begins to DC
brake,
Output
voltage
time
time
DC brake
time
Running
command
DC
brake
current
Output freq
Output freq
DC brake current as stop
DC brake time as stop
Running
command
Output
voltage
Start freq of DC brake as stop
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...