YX3000 Senseless Vector Type Inverter Manual
- 140 -
Restart the motor in running
Setup start mode as speed tracking
restart
Mains voltage is too low
Check mains voltage
Too heavy load
Select inverter with proper capacity
E-10
Motor
overload
V/F curve setup is not suitable Adjust V/F curve
Mains voltage is too low
Check mains voltage
General motor runs at low
speed with heavy load for long
term
Use a special motor for long term
running
Wrong
setting
of
motor
overload protection factor
Set the factor right
Motor chocked or sudden
change of load
Check load
E-11
Under voltage
in running
Mains voltage is too low
Check mains voltage
Fault
code
Type of faults
Possible fault reasons
Troubleshooting
E-12
Inverter
module
protection
Inverter over current
Refer to over current
troubleshooting
Output 3-phase fault or ground
short
Re-wiring
Air duct obstruction or fan
damaged
Clean air duct or replace a new fan
Environment temperature too
high
Decrease environment temperature
Control board connecting wire
or plug-in unit loose
Check and re-wiring
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...