YX3000 Senseless Vector Type Inverter Manual
- 136 -
super user password is 2644.
6.11 Vector Control Parameter (PA Group)
PA.00
Motor parameter Auto
tuning function
Range
:
0, 1
0
0
:
Inaction
1
:
Static auto-tuning
When settings PA.00=1, inverter show "FUN0 ", then press " FWD " key to start inverter
parameter auto-tuning. When keyboard display " FUN1 ", auto tuning is complete.
PA.01
Motor rated voltage
Range
:
0
~
400V
Depends on
model type
PA.02
Motor rated current
Range
:
0.01
~
500.00A
Depends on
model type
PA.03
Motor rated frequency
Range
:
1
~
500Hz
Depends on
model type
PA.04
Motor rated rotating speed
Range
:
1
~
9999 r/min
Depends on
model type
PA.05
Motor poles number
Range
:
2
~
16
Depends on
model type
PA.06
Motor stator inductance
Range
:
0.1
~
5000.0mH
Depends on
model type
PA.07
Motor rotor inductance
Range
:
0.1
~
5000.0mH
Depends on
model type
PA.08
Motor stator and rotor
mutual inductance
Range
:
0.1
~
5000.0mH
Depends on
model type
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...