YX3000 Senseless Vector Type Inverter Manual
- 94 -
Note
:
When ASCII mode is selected, please select data format as 0~2, that data place is 7.
When RTU mode is selected, please select data format as 3~5, that data place is 8.
P3.10
Local adress
Range: 0
~
248
1
This function is used to mark the address of inverter itself in serial port communication mode.
0 Broadcast address. When the inverter works as a slave, if it receives address command as
0, it means the inverter is receiving broadcast command and unnecessary to respond the
host.
248 Host address. When the inverter works as a host, set P3.10=248, the host inverter is
able to send broadcast command to other slave inverters so as to achieve multi-machine
interaction
。
P3.11
Communication
overtime detection
time
Range: 0.0
~
1000.0S
0.0S
When serial port communication is failed, if the duration exceeds the set value of this function,
the inverter will conclude that there is a communication failure.
As set value is 0, the inverter will not detect the serial port communication signal, that this
function is invalid.
P3.12
Local response delay
Range: 0
~
1000ms
5ms
Local response delay is the time from serial port receiving the command from the upper
computer and executing the command to responding the upper computer.
P3.13
Multi-running
proportion
Range: 0.01
~
1.00
1.00
This function code is used to set the scale factor of inverter received frequency set command
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...