YX3000 Senseless Vector Type Inverter Manual
- 134 -
P9.08
Terminal UP/DOWN and
Fan control selection
Range
:
000
~
111
0
Unite digit:
0
:
Inverter fan operation, shutdown after 1 minutes after the fan stops running.
1
:
Power on the fan operation
Ten digit:
0: When Frequency is set by Terminal UP/DOWN (P0 .01=3), inverter will save the frequency
value after power off. When inverter restarts, the initial frequency will be the last saving
frequency.
1: When Frequency is set by Terminal UP/DOWN (P0 .01=3), inverter will not save the
frequency value after power off. The Intial frequency setting is 0HZ
Hundred digit:
0: Inverter run/ stop is set by Terminal (P0.03=1). After power cut off and switch on, inverter
will run or stop according to Terminal setting.
1: Inverter run/ stop is set by Terminal (P0.03=1). After power cut off and switch on, inverter
will stop.
P9.09
Multi-function terminal
filtering time
Range
:
0
~
4
1
The parameter is used for multi-function terminals (X1-X8) signal filtering. Increasing the
value, the effect of filtering will be improved, but the Terminal response time will be longer.
Reducing the value, the effect of filtering will get worse and Terminal response time is short.
In some motion control application which requires instant action, parameter P9.09 should set
0
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...