YX3000 Senseless Vector Type Inverter Manual
- 78 -
P0.06
Max. output freq.
range
:
50.00Hz
~
500.0Hz
50.00Hz
P0.07
Basic running freq.
range
:
1.00Hz
~
500.00Hz
50.00Hz
P0.08
Max. output voltage
Rated voltage
range
:
1
~
480V
Rated voltage
Max. output freq. is inverter highest output frequency allowed shown as Fig. 6-2 Fax.
Basic running freq. is the lowest output frequency corresponding to the highest output
voltage of inverter. Generally, it is motor rated frequency shown as Fig.6-2 FB.
Max. output voltage is the output voltage corresponding to inverter outputs basic running
frequency. Generally, it is motor rated voltage shown as Fig.6-2 Amax.
Fig.6-2 Fmax/FB/Vmax0V
FH,FL are the upper limit frequency and lower limit frequency, defined by P0.19,P0.20
function parameter.
P0.09
Torque boost
Range
:
0.0
%~
30.0
%
2.0
%
In switching process between forward
and reverse running, the transition time
as Fig.6-1 t1 is defined as FWD/REV
dead time. The inverter outputs 0 freq.
during transition time.
Time
t
1
Output frequency
Fig.6-1 FWD/REV dead time
Output Freq.
FL
FB FH Fmax
Vmax
Output voltage
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...