YX3000 Senseless Vector Type Inverter Manual
- 77 -
8
:
Combination given (refer to function parameter P3.00).
P0.02
Initial digital set freq.
Range: Lower limit freq. ~
Upper limit freq.
50.00Hz
When Freq control channel selection setting (P0.01=1, 2, 3, 4), P0.02 parameter defines the
initial digital set frequency.
P0.03
Running command mode
selection
Range
:
0, 1,2
0
0:
Use control panel key RUN, STOP/RESET, JOG to operate the inverter.
1:
Terminal control mode. Use control terminal FWD, REV, X1~X6, etc. to operate the
inverter.
2
:
Serial port control mode. Operate the inverter via serial port RS485 in remote control
mode.
Note:
Running command mode can be switched by changing P0.03 parameter in stopping or
running state. Please use this function in caution.
P0.04
Running direction setting
Range
:
00
~
11
0
This function is effective in panel control mode, terminal control mode, and serial port control
mode.
LED unit’s digit:
0
:
Running forward
1
:
Running reverse
LED ten’s digit:
0
:
Reverse allowed
1
:
Reverse prohibited
P0.05
FWD/REV dead time
Range
:
0.0
~
120.0s
0.0s
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...