YX3000 Senseless Vector Type Inverter Manual
- 82 -
Note:
(1) The inverter has 7 Acc/Dec time. Herein just 1 Acc/Dec is defined. The other 2~7
Acc/Dec time are defined by P3.14~P3.25 function parameter.
(2) It can select time unit by P0.09 for all 1~7 Acc/Dec time. The factory default setting
unit is second.
P0.19
Upper limit freq.
Range: Lower limit freq. ~ highest
output freq.
50.00Hz
P0.20
Lower limit freq.
Range: 0.00Hz ~ Upper limit freq.
0.00HZ
P0.21
Lower limit freq.
running mode
Range: 0: running at lower limit
freq. 1: stopping
0
P0.19,P0.20 parameter defines the upper and lower limit of output frequency. FH,FL is upper
limit frequency and lower limit frequency respectively shown as Fig.6-2.
When actual setting frequency is lower than lower limit freq., the inverter output frequency will
decrease in Dec time which has been set. As it reaches the lower limit frequency, if P0.21=0 ,
the inverter will run at lower limit frequency. If P0.21=1, the inverter will keep decreasing the
output frequency to 0.
P0.22
V/F curve setting
Range: 0
~
4
0
P0.23
V/F Freq. F3
Range: P0.25-P0.07 basic Freq.
0.00Hz
t
1
t
2
time
Output Freq
Upper limit
Fig.6-6 Acc/Dec time
Содержание YX2000
Страница 18: ...YX3000 Senseless Vector Type Inverter Manual 17 2 4 Dimensions W H W1 H1 D a Inverters below 7 5KW...
Страница 19: ...YX3000 Senseless Vector Type Inverter Manual 18 W W1 H H1 D b Inverters from 11KW to 90 KW...
Страница 20: ...YX3000 Senseless Vector Type Inverter Manual 19 W1 H2 H1 D W H c Inverters from 110KW to 250 KW...
Страница 21: ...YX3000 Senseless Vector Type Inverter Manual 20 W H D d Inverters from 285KW to 315KW...
Страница 22: ...YX3000 Senseless Vector Type Inverter Manual 21 W H D e Inverters from 350KW to 630KW...