YX3000 Senseless Vector Type Inverter Manual
- 10 -
turn off the contactor when the AC drive is active. Otherwise, modules inside the AC drive
may be damaged.
1.2.8 Applied with the Rated Voltage
Apply YX3000 with the rated voltage. Failure to comply will damage inverter. If required, take
a transformer to boost or step-down voltage.
1.2.9 Do Not Apply a 3-Phase Input Inverter to 2-Phase Input Applications
Do not apply a 3-phase input FR inverter to 2-phase input applications. Otherwise, it will
result in faults or damage inverter.
1.2.10 Lightning Protection
YX3000 has integrated lightning over-current protection device which has certain
self-protection capacity against the lightning. Additional protection devices have to be
installed between inverter and power supply in the area where lightning occurs frequently.
1.2.11 Altitude De-rating
In places where the altitude is above 1000 m and the cooling effect reduces due to thin air,
it is necessary to de-rate the AC drive. Contact YUANXIN for technical support.
80%
90%
100%
1000
2000
3000
4000
Iout
(米)
1.2.12 some special usages