2 : Enabled Only when Rotating REV
Note:
When
n3-23 = 1, 2
, the drive enables overexcitation only in the direction of motor rotation in which a regenerative load is applied. Increased
motor loss can decrease
ov [Overvoltage]
faults.
◆
n5: Feed Forward Control
Feed forward control increases the responsiveness of acceleration and deceleration as specified by the speed
reference.
Increase the values set in
C5-01 and C5-03 [ASR Proportional Gain]
to apply feed forward control to machines that
have low rigidity and are possible to have hunting and vibration or to machines that have a large quantity of inertia.
Refer to
for more information about parameters related to feed forward control.
Set
A1-02 = 6 [Control Method Selection = Advanced Open Loop Vector Control for PM]
to enable feed forward
control.
Note:
•
You cannot use feed forward control to increase responsiveness in applications where you apply loads externally during run at constant
speed.
•
You cannot use feed forward control with motor 2.
Figure 2.128 Configure Feed Forward Control
■
Before You Use Feed Forward Control
Do one of these procedures before you use feed forward control.
•
Run Auto-Tuning to set motor parameters.
When you cannot do Auto-Tuning, manually set motor parameters with the information on the motor nameplate or
test reports. Set the
E2 parameters
for induction motors. Set the
E5 parameters
for PM motors.
•
Set
C5 parameters [Automatic Speed Regulator (ASR)]
individually to adjust the speed control loop (ASR).
•
If you can connect a motor to a machine and rotate it during Auto-Tuning, do Inertia Tuning.
The drive automatically adjusts feed forward parameters during Inertia Tuning.
•
If you cannot do Inertia Tuning, refer to
and set the parameters related to feed forward control
individually.
■
n5-01: Feed Forward Control Selection
No.
(Hex.)
Name
Description
Default
(Range)
n5-01
(05B0)
Feed Forward Control
Selection
Sets the feed forward function.
0
(0, 1)
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...