2.8 H: Terminal Function Selection
330
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
4E: Braking Transistor Fault (rr)
Setting Value
Function
Description
4E
Braking Transistor Fault (rr)
The terminal activates when the internal braking transistor overheats and the drive detects an
rr [Dynamic Braking Transistor Fault]
fault.
■
4F: Braking Resistor Overheat (rH)
Setting Value
Function
Description
4F
Braking Resistor Overheat
(rH)
The terminal activates when the braking resistor overheats and the drive detects an
rH [Braking Resistor Overheat]
fault.
The braking resistor overheats when the deceleration time is short and there is too much motor regeneration energy.
■
61: Pole Position Detection Complete
Setting Value
Function
Description
61
Pole Position Detection
Complete
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM motor.
■
62: Modbus Reg 1 Status Satisfied
Setting Value
Function
Description
62
Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by
H2-08 [Modbus Register 1 Bit Select]
for the MEMOBUS register address set with
H2-07 [Modbus Register 1 Address Select]
activates.
■
63: Modbus Reg 2 Status Satisfied
Setting Value
Function
Description
63
Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by
H2-10 [Modbus Register 2 Bit Select]
for the MEMOBUS register address set with
H2-09 [Modbus Register 2 Address Select]
activates.
■
66: Comparator1
Setting Value
Function
Description
66
Comparator1
The terminal activates if the monitor value set with
H2-20 [Comparator 1 Monitor Selection]
is in range of the values of
H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit]
for the time set in
H2-24 [Comparator 1 On-Delay Time]
.
A - H2-24
[Comparator 1 On-Delay Time]
B - H2-25
[Comparator 1 Off-Delay Time]
Figure 2.85 Comparator 1 Output Time Chart
Note:
The drive compares the monitors set with
H2-20
as absolute values.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...