2.8 H: Terminal Function Selection
344
YASKAWA
TOEPYAIGA5002A GA500 Programming
Figure 2.95 Analog Output Gain/Bias Configuration Example 2
Calibrate Terminal AM
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show
H4-02 [Terminal AM Analog Output Gain]
on the keypad.
Terminal AM outputs the analog signal when the monitor item that you set in
H4-01 [Terminal AM Analog
Output Select]
is 100%.
2. Adjust
H4-02
while referencing the meter scale connected to terminal AM.
3. Show
H4-03 [Terminal AM Analog Output Bias]
on the keypad.
The analog signal at the time when the monitor item selected with
H4-01
is 0% is output from terminal AM.
4. Adjust
H4-03
while referencing the meter scale connected to terminal AM.
■
H4-01: Terminal AM Analog Output Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-01
(041D)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
102
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-01 = 102
to monitor
U1-02 [Output Frequency]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
■
H4-02: Terminal AM Analog Output Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-02
(041E)
RUN
Terminal AM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
100.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of 10 V (or 20 mA). Use
H4-07 [Terminal AM Signal
Level Select]
to set the signal level.
■
H4-03: Terminal AM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-03
(041F)
RUN
Terminal AM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of 10 V (or 20 mA). Use
H4-07 [Terminal AM Signal
Level Select]
to set the signal level.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...