1.22 Parameters Changed by PM Motor Code Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
135
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-06
PM d-axis Inductance (mH/phase)
mH
6.59
4.96
3.83
3.33
2.38
E5-07
PM q-axis Inductance (mH/phase)
mH
8.55
6.12
4.65
4.50
3.15
E5-09
PM Back-EMF Vpeak (mV/(rad/
s))
mVs/rad
391.5
384.4
372.1
421.3
410.9
E5-24
PM Back-EMF L-L Vrms (mV/
rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Output Voltage
V
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
E1-09
Minimum Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
L3-24
Motor Accel Time @ Rated
Torque
s
0.088
0.073
0.062
0.091
0.092
n5-02
Motor Inertia Acceleration Time
s
0.088
0.073
0.062
0.091
0.092
n8-49
Heavy Load Id Current
%
-15.3
-13.9
-14.4
-17.9
-15.9
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Table 1.19 SSR1 Series Motor Code Setting for Specification of 400 V at 1150 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection
-
1432
1433
1435
1436
1438
143A
Voltage Class
V
400
400
400
400
400
400
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min
-1
1150
1150
1150
1150
1150
1150
E5-02
PM Motor Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Motor Rated Current
(FLA)
A
0.94
1.51
3.00
4.43
7.08
10.10
E5-04
PM Motor Pole Count
-
6
6
6
6
6
6
E5-05
PM Motor Resistance (ohms/
phase)
Ω
19.320
10.800
4.456
2.044
1.483
1.215
E5-06
PM d-axis Inductance (mH/
phase)
mH
194.70
129.20
76.88
48.60
37.58
44.54
E5-07
PM q-axis Inductance (mH/
phase)
mH
252.84
160.90
97.52
61.40
47.65
56.26
E5-09
PM Back-EMF Vpeak (mV/
(rad/s))
mVs/rad
640.9
654.1
728.8
688.9
702.0
861.5
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Minimum Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
2.9
L3-24
Motor Accel Time @ Rated
Torque
s
0.062
0.044
0.080
0.090
0.067
0.072
n5-02
Motor Inertia Acceleration
Time
s
0.062
0.044
0.080
0.090
0.067
0.072
n8-49
Heavy Load Id Current
%
-8.8
-9.9
-9.3
-10.0
-12.8
-12.3
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...