416
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
n8-02: Pole Alignment Current Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-02
(0541)
Pole Alignment Current
Level
Sets the current at the time of polar attraction as a percentage where
E5-03 [motor rated current]
is
100%. Usually it is not necessary to change this setting.
80%
(0 - 150%)
The drive uses the polar pull-in current to attract the rotor after it detects the initial rotor position. When you increase
the value of
n8-02
, the starting torque also increases.
•
If the motor does not track correctly at the time of the polar attraction, increase the value in 10% increments.
•
If the motor oscillates at the time of the polar attraction, decrease the value in 10% increments.
■
n8-11: Observer Calculation Gain 2
No.
(Hex.)
Name
Description
Default
(Range)
n8-11
(054A)
Observer Calculation Gain 2
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Determined by n8-72
(0.0 - 1000.0)
Note:
When
n8-72 = 0 [Speed Estimation Method Select = Method 1]
, the default value is 50.0. When
n8-72 = 1 [Method 2]
, the default value is
150.0.
■
n8-14: Polarity Compensation Gain 3
No.
(Hex.)
Name
Description
Default
(Range)
n8-14
(054D)
Expert
Polarity Compensation Gain
3
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
1.000
(0.000 - 10.000)
■
n8-15: Polarity Compensation Gain 4
No.
(Hex.)
Name
Description
Default
(Range)
n8-15
(054E)
Expert
Polarity Compensation Gain
4
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
0.500
(0.000 - 10.000)
■
n8-21: Motor Back-EMF (Ke) Gain
No.
(Hex.)
Name
Description
Default
(Range)
n8-21
(0554)
Expert
Motor Back-EMF (Ke) Gain
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
0.90
(0.80 - 1.00)
■
n8-23: ACR q Gain @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-23
(0556)
Expert
ACR q Gain @PoleEst
Sets the proportional gain for current regulator q-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
0
(0 - 2000)
■
n8-24: ACR q Integral Time @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-24
(0557)
Expert
ACR q Integral Time
@PoleEst
Sets the integral time for current regulator q-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...