2.8 H: Terminal Function Selection
334
YASKAWA
TOEPYAIGA5002A GA500 Programming
Note:
•
Refer to
Multi-Function Analog Input Terminal Settings on page 337
for the analog input setting values.
•
When you will not use the terminal, set
H3-40 to H3-42 = F
. Parameters
H3-40
to
H3-42
do not support the through mode.
•
You cannot use
H3-40
to
H3-42
to set these MFAI functions:
H3-xx Setting Value
Function
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2
◆
H3: MFAI Parameters
■
H3-01: Terminal A1 Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0
(0, 4)
0 : 0 to 10V (Lower Limit at 0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
4 : -10 to +10V (Bipolar Reference)
The voltage signal is -10 Vdc to 10 Vdc. Signals of both positive and negative polarities are enabled. When this
setting is used as the frequency reference, the motor runs reverse when the Forward run command is input, or runs
forward when the Reverse run signal is input, while the signal is a negative number due to gain and bias.
■
H3-02: Terminal A1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 32)
■
H3-03: Terminal A1 Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
This parameter sets the quantity of reference for the function set for terminal A1 as a percentage when 10 V (or 20
mA) is input.
Use this parameter and
H3-04 [Terminal A1 Bias Setting]
to adjust the characteristics of the analog input signal to
terminal A1.
■
H3-04: Terminal A1 Bias Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...