YASKAWA
TOEPYAIGA5002A GA500 Programming
417
■
n8-25: ACR q Limit @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-25
(0558)
Expert
ACR q Limit @PoleEst
Sets the q-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
0%
(0 - 150%)
■
n8-26: ACR d Gain @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-26
(0559)
Expert
ACR d Gain @PoleEst
Sets the proportional gain for current regulator d-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
500
(0 - 2000)
■
n8-27: ACR d Integral Time @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-27
(055A)
Expert
ACR d Integral Time
@PoleEst
Sets the integral time for current regulator d-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
■
n8-28: ACR d Lim @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-28
(055B)
Expert
ACR d Lim @PoleEst
Sets the d-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
100%
(0 - 150%)
■
n8-35: Initial Pole Detection Method
No.
(Hex.)
Name
Description
Default
(Range)
n8-35
(0562)
Initial Pole Detection
Method
Sets how the drive detects the position of the rotor when the motor starts.
Determined by A1-02
(0 - 2)
Note:
•
When you use an SPM motor, set
n8-35 = 0
. When you use an IPM motor, set
n8-35 = 0 to 2
.
•
When you set
n8-35 = 1
, do High Frequency Injection Auto-Tuning.
•
When you set
n8-35 = 0 or 2
, always evaluate the drive with the equipment being used for the application. If the drive incorrectly detects
the polarity, the motor can rotate in the direction opposite of the Run command.
0 : Pull-in
Starts the rotor with pull-in current.
1 : High Frequency Injection
Injects high frequency to detect the rotor position. This setting can cause a loud excitation sound when the motor
starts.
Note:
When you set
1
, do High Frequency Injection Auto-Tuning.
2 : Pulse Injection
Inputs the pulse signal to the motor to detect the rotor position.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...