TOEPYAIGA5002A GA500 Programming
207
■
C1-07: Acceleration Time 4
No.
(Hex.)
Name
Description
Default
(Range)
C1-07
(0206)
RUN
Acceleration Time 4
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-08: Deceleration Time 4
No.
(Hex.)
Name
Description
Default
(Range)
C1-08
(0207)
RUN
Deceleration Time 4
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-09: Fast Stop Time
No.
(Hex.)
Name
Description
Default
(Range)
C1-09
(0208)
RUN
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
10.0 s
(0.0 - 6000.0 s)
Note:
•
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
•
When
L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1]
and you do KEB Auto-Tuning, the drive will
automatically set
C1-09
. If you must not change the Fast Stop time, do not do KEB Auto-Tuning.
The Fast Stop function will be triggered in the following circumstances.
•
The Fast Stop operation will be triggered by the input of the Fast Stop command via the multi-function digital input
terminal.
•
The Fast Stop operation is will be triggered when by the input of the Fast Stop command is input via the multi-
function digital input terminal.
Set
H1-xx = 15, 17 [MFDI Function Select = Fast Stop (N.O.), Fast Stop (N.C.)]
.
When the Fast Stop command is input, the Fast Stop operation will be triggered at the deceleration time set to
C1-09
.
The drive cannot be restarted after initiating a Fast Stop operation until deceleration is complete. Complete
deceleration and cycle the Run command to clear the Fast Stop input.
The terminal set for
H2-xx = 4C [MFDO Function Select = During Fast Stop]
will be ON during Fast Stop.
Note:
Decelerating too quickly can cause an
ov [Overvoltage]
fault that shuts off the drive while the motor to coasts to a stop. Set a Fast Stop time
in
C1-09
that prevents motor coasting and makes sure that the motor stops quickly and safely.
■
C1-10: Accel/Decel Time Setting Units
No.
(Hex.)
Name
Description
Default
(Range)
C1-10
(0209)
Accel/Decel Time Setting
Units
Sets the setting units for
C1-01 to C1-08 [Accel/Decel Times 1 to 4]
,
C1-09 [Fast Stop Time]
,
L2-06
[Kinetic Energy Backup Decel Time]
, and
L2-07 [Kinetic Energy Backup Accel Time]
.
1
(0, 1)
0 : 0.01 s (0.00 to 600.00 s)
Sets acceleration and deceleration times in 0.01 s units. The setting range is 0.0 to 6000.0 s.
If one of these parameters is set to 1000.0 s or longer, you cannot set
C1-10 = 0
:
•
C1-01 to C1-09
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...