40
YASKAWA
TOEPYAIGA5002A GA500 Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F1-11
(038A)
Speed Deviation Detect
DelayTime
Sets the length of time that the difference between the frequency reference and speed
feedback must be more than the level in
F1-10
to cause
dEv [Speed Deviation]
.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
0.5 s
(0.0 - 10.0 s)
F1-14
(038D)
Encoder Open-Circuit
Detect Time
Sets the length of time that the drive must not receive a pulse signal to cause
PGo
[Encoder (PG) Feedback Loss]
.
Note:
Motor speed and load conditions can cause
ov [Overvoltage]
and
oC [Overcurrent]
faults.
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
2.0 s
(0.0 - 10.0 s)
◆
F6: Communication Options
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive
detects
bUS [Option Communication Error]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
1
(0 - 5)
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets the conditions at which
EF0 [Option Card External Fault]
is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
F6-03
(03A4)
Comm External Fault
(EF0) Select
Sets the method to stop the motor or let the motor continue operating when the drive
detects
EF0 [Option Card External Fault]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
F6-04
(03A5)
bUS Error Detection
Time
Sets the delay time for the drive to detect
bUS [Option Communication Error]
.
Note:
When you install a CC-Link option (SI-C3) to the drive, the setting value changes to
0.0 s.
2.0 s
(0.0 - 12.0 s)
F6-06
(03A7)
Torque Reference/Limit
by Comm
Sets the function that enables and disables the torque reference and torque limit received
from the communication option.
0 : Disabled
1 : Enabled
0
(0, 1)
F6-07
(03A8)
Multi-Step Ref @
NetRef/ComRef
Sets the function that enables and disables the multi-step speed reference when the
freqency reference source is NetRef or ComRef (communication option card or
MEMOBUS/Modbus communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
1
(0, 1)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized
with
A1-03 [Initialize Parameters]
.
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...