Figure 2.119 Stall Prevention Level during Run with Analog Input
■
L3-11: Overvoltage Suppression Select
No.
(Hex.)
Name
Description
Default
(Range)
L3-11
(04C7)
Overvoltage Suppression
Select
Sets the overvoltage suppression function.
0
(0, 1)
0 : Disabled
The drive does not adjust the regenerative torque limit or the output frequency. If you apply a regenerative load, the
drive can detect an
ov [Overvoltage]
fault. Use this setting with a dynamic braking option.
1 : Enabled
When a regenerative load increases the DC bus voltage, the drive decreases the regenerative torque limit and
increases the output frequency to prevent
ov
■
L3-17: DC Bus Regulation Level
No.
(Hex.)
Name
Description
Default
(Range)
L3-17
(0462)
DC Bus Regulation Level
Sets the target value for the DC bus voltage when the overvoltage suppression function and the Decel
Stall Prevention function (Intelligent Stall Prevention) are active.
200 V Class: 375 V, 400 V:
750 V
(200 V Class: 150 to 400 V,
400 V Class: 300 to 800 V)
Note:
This value is initialized when
E1-01 [Input AC Supply Voltage]
is changed.
Sets this parameter for any of the following circumstances.
•
L3-11 = 1 [OV Suppression Function Select = Enabled]
.
•
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
.
■
L3-20: DC Bus Voltage Adjustment Gain
No.
(Hex.)
Name
Description
Default
(Range)
L3-20
(0465)
Expert
DC Bus Voltage Adjustment
Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
Set one of these parameters to enable L3-20:
•
L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2]
•
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
•
L3-11 = 1 [OV Suppression Function Select = Enabled]
•
H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 (N.O./N.C.)]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...