2.8 H: Terminal Function Selection
290
YASKAWA
TOEPYAIGA5002A GA500 Programming
When the setting value is F, the function is disabled.
■
H1-25: Terminal S5 Function Select 2
No.
(Hex.)
Name
Description
Default
(Range)
H1-25
(0B74)
Terminal S5 Function
Selection 2
Sets the second function for MFDI terminal S5.
F
(1 - 19F)
When MFDI terminal S5 activates, it will operate the function set to
H1-05 [Terminal S5 Function Selection]
and the
function set to
H1-25
at the same time.
When the setting value is
F
, the function is disabled.
■
H1-26: Terminal S6 Function Select 2
No.
(Hex.)
Name
Description
Default
(Range)
H1-26
(0B75)
Terminal S6 Function
Selection 2
Sets the second function for MFDI terminal S6.
F
(1 - 19F)
When MFDI terminal S6 activates, it will operate the function set to
H1-06 [Terminal S6 Function Selection]
and the
function set to
H1-26
at the same time.
When the setting value is
F
, the function is disabled.
■
H1-27: Terminal S7 Function Select 2
No.
(Hex.)
Name
Description
Default
(Range)
H1-27
(0B76)
Terminal S7 Function
Selection 2
Sets the second function for MFDI terminal S7.
F
(1 - 19F)
When MFDI terminal S7 activates, it will operate the function set to
H1-07 [Terminal S7 Function Selection]
and the
function set to
H1-27
at the same time.
When the setting value is
F
, the function is disabled.
■
MEMOBUS/Modbus MFDI 1 to 3 Function Selection
You can set the function for the MFDI to MEMOBUS register
bit 0 to 2
of
[15C0(Hex.)]
. Use
H1-40 to H1-42
[Extend MFDI Function Selection]
to select the bit function for each bit.
Note:
•
Refer to
MFDI Setting Values on page 291
for more information about MFDI setting values.
•
You cannot set values
0 [3-Wire Sequence]
and
20 to 2F [External Fault]
for
H1-40
to
H1-42
.
•
When you will not use
H1-40
to
H1-42
, set them to
F [Through Mode]
.
■
H1-40: Mbus Reg 15C0h bit0 Input Func
No.
(Hex.)
Name
Description
Default
(Range)
H1-40
(0B54)
Mbus Reg 15C0h bit0 Input
Func
Sets MFDI function to set to
bit 0
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 19F)
■
H1-41: Mbus Reg 15C0h bit1 Input Func
No.
(Hex.)
Name
Description
Default
(Range)
H1-41
(0B55)
Mbus Reg 15C0h bit1 Input
Func
Sets MFDI function to set to
bit 1
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 19F)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...