YASKAWA
TOEPYAIGA5002A GA500 Programming
397
1 : Proportional & Integral control
The torque limit function always uses integral control. Use this setting when a very accurate torque limit is necessary
during speed changes, for example in winding machine applications.
If you make the torque limit the most important, it can:
•
Increase the acceleration and deceleration times.
•
Not let the motor speed reach the frequency reference value during run at constant speed.
■
L7-16: Torque Limit Process at Start
No.
(Hex.)
Name
Description
Default
(Range)
L7-16
(044D)
Torque Limit Process at Start
Assigns a time filter to allow the torque limit to build at start.
1
(0, 1)
0 : Disabled
There is torque limit at start without a delay time.
Use this setting to maximize the response time when sudden acceleration or deceleration at start is necessary.
1 : Enabled
There is a delay time of 64 ms at start to build the torque limit.
◆
L8: Drive Protection
L8 parameters
set protective functions that prevent faults such as overheating, phase loss, and ground faults.
■
L8-01: 3% ERF DB Resistor Protection
No.
(Hex.)
Name
Description
Default
(Range)
L8-01
(04AD)
3% ERF DB Resistor
Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0
(0, 1)
0 : No
Disables braking resistor protection. Use this setting for dynamic braking options that are not Yaskawa ERF series
braking resistors.
1 : Yes
Enables protection for Yaskawa ERF series braking resistors.
Note:
Set
L8-01 = 1
and
H2-01 to H2-03 = D [MFDO Function Select = Braking Resistor Fault]
. Use a sequence to turn OFF power with MFDO.
■
L8-02: Overheat Alarm Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-02
(04AE)
Overheat Alarm Level
Sets the
oH
detection level in temperature.
Determined by o2-04, C6-01
(50 - 150 °C)
If the heatsink temperature is more than the temperature set in this parameter, the drive detects an overheat pre-alarm.
To enable this function, set one of
H2-01 to H2-03 [MFDO Function Select]
to
20 [Drive Overheat Pre-Alarm (oH)]
.
If the temperature increases to the overheat fault level, the drive will trigger an
oH1 [Heatsink Overheat]
fault and
stop operation.
■
L8-03: Overheat Pre-Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets the operation of drives when an
oH
alarm is detected.
3
(0 - 4)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...