94
YASKAWA
TOEPYAIGA5002A GA500 Programming
1.17
U: Monitors
◆
U1: Operation Status Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U1-01
(0040)
Frequency Reference
Shows the frequency reference value. Parameter
o1-03 [Keypad Display Unit Selection]
sets the
display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-02
(0041)
Output frequency
Shows the output frequency. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-03
(0042)
Output Current
Shows the actual output current.
The keypad shows the value of
U1-03
in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is
“
8192 = drive rated current (A)
”
. Calculate the
current from the monitor value that is in at MEMOBUS/Modbus communications using
“
Numerals
being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
•
0.01 A units: B001 - B018, 2001 - 2042, 4001 - 4023
•
0.1A units: 2056 - 2082, 4031 - 4060
10 V = Drive rated current
U1-04
(0043)
Control method selection
Shows the drive control method.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
No signal output available
U1-05
(0044)
Motor Speed
Shows the detected motor speed. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display
units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-06
(0045)
Output Voltage Ref
Shows the output voltage reference.
Unit: 0.1 V
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
U1-07
(0046)
DC Bus Voltage
Shows the DC bus voltage.
Unit: 1 V
200 V class: 10 V = 400 V
400 V class: 10 V = 800 V
U1-08
(0047)
Output Power
Shows the internally-calculated output power.
When you change
A1-02 [Control Method Selection]
, it will also change the signal level of the
analog output.
•
A1-02 = 0: Drive capacity (kW)
•
A1-02 = 2:
Motor Rated Power [E2-11]
(kW)
•
A1-02 = 5, 6:
PM Motor Rated Power [E5-02]
(kW)
•
A1-02 = 8:
Motor Rated Power [E9-07]
(kW)
Unit: When the drive model changes, the display units for this parameter also change.
•
0.01 A units: B001 to B018, 2001 to 2042, 4001 to 4023
•
0.1A units: 2056 - 2082, 4031 - 4060
10 V: Drive capacity (motor
rated power) kW
(0 V to +10 V)
U1-09
(0048)
Torque Reference
Shows the internal torque reference value.
Unit: 0.1%
10 V = Motor rated torque (0
V to +10 V)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...